« back Certified Uninterruptible Power Supplies
CyberPower - PR5000LCDRTXL5U
-
Power Conversion Mechanism:Static
-
Minimum Configuration Tested Model Number:PR5000LCDRTXL5U
-
Rated Output Power (W):4,500
-
Active Output Power Rating Minimum Configuration (W):4500
-
Apparent Output Power Rating Minimum Configuration (VA):5000
-
Topology (ac):Line Interactive
-
Topology and Product Type Combined:ac Line Interactive (VI)
-
Application:Consumer
-
Rated Input Voltage (V rms):208-240
-
Rated Input Frequency (Hz):50-60
-
Rated Output Voltage (V):208-240
-
Rated Output Frequency (Hz):50-60
-
Rack Mountable:No
-
Height (mm):433
-
Width (mm):220
-
Depth (mm):645
-
Normal Mode(s) Input Dependency Characteristic (ac):Voltage Independent
-
Modular UPS:No
-
Number of Normal Modes:Single-normal-mode
-
Default Normal Mode (ac):Voltage Independent
-
Test Input Voltage (V rms):230
-
Test Input Frequency (Hz):50
-
Test Output Voltage (V):230
-
Test Output Frequency (Hz):50
-
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac):5.38
-
Efficiency at 25% Load Min Config Lowest Dependency (ac):98.8
-
Efficiency at 50% Load Min Config Lowest Dependency (ac):98.7
-
Efficiency at 75% Load Min Config Lowest Dependency (ac):98.5
-
Efficiency at 100% Load Min Config Lowest Dependency (ac):98.3
-
Weighted Efficiency Calc Min Config Lowest Dependency:98.5
-
Efficiency (%):98.5
-
Modular UPS Module Tested Model Number:PR5000LCDRTXL5U
-
Energy Storage Mechanism:Battery
-
Energy Storage System Technology:Valve Regulated Lead-acid Battery
-
Energy Storage System Configuration:Integral
-
Energy Storage System Removable to Another Room:No
-
Energy Storage System Runtime at 100% Load (min.):N/A
-
Energy Storage System Runtime at 50% Load (min.):N/A
-
Energy Storage System Warranty (yrs):3
-
Energy Storage System Information URL:N/A
-
Network Connections Available:None
-
Communication Protocols:None
-
Data Provided via Network Communication:No Network Communication
-
Data Visually Displayed:Output Current,Output Active Power,Output Power Factor,Output Voltage
-
Output Energy Meter Integral or External to the UPS:No Energy Meter
-
Meets ENERGY STAR Optional Metering Requirements:N/A
-
Manufacturer Take Back Program:Yes
-
Model Web Page URL:N/A
-
Meets Efficiency Requirements Without the Metering Incentive :N/A
-
Test Method Guidelines:N/A
-
Date Available on Market:04/01/2016
-
Date Qualified:03/23/2016
-
Markets:United States, Europe, Canada
Additional Model Information
PR5000LCDRTXL5UTAA,PR5000LCDRTXL5UTAA,
Follow us