« back Certified Uninterruptible Power Supplies
CyberPower - OR2200LCDRT2U
-
Power Conversion Mechanism:Static
-
Minimum Configuration Tested Model Number:OR2200LCDRT2U
-
Rated Output Power (W):1,320
-
Active Output Power Rating Minimum Configuration (W):1320
-
Apparent Output Power Rating Minimum Configuration (VA):2000
-
Topology (ac):Line Interactive
-
Topology and Product Type Combined:ac Line Interactive (VI)
-
Application:Commercial,Consumer,Data Center
-
Rated Input Voltage (V rms):90-140
-
Rated Input Frequency (Hz):47-63
-
Rated Output Voltage (V):108-132
-
Rated Output Frequency (Hz):49-61
-
Rack Mountable:Yes
-
Height (mm):88
-
Width (mm):438
-
Depth (mm):400
-
Normal Mode(s) Input Dependency Characteristic (ac):Voltage Independent
-
Modular UPS:No
-
Number of Normal Modes:Single-normal-mode
-
Default Normal Mode (ac):Voltage Independent
-
Test Input Voltage (V rms):120
-
Test Input Frequency (Hz):60
-
Test Output Voltage (V):120
-
Test Output Frequency (Hz):60
-
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac):3.5
-
Efficiency at 25% Load Min Config Lowest Dependency (ac):98.7
-
Efficiency at 50% Load Min Config Lowest Dependency (ac):98.9
-
Efficiency at 75% Load Min Config Lowest Dependency (ac):98.8
-
Efficiency at 100% Load Min Config Lowest Dependency (ac):98.6
-
Weighted Efficiency Calc Min Config Lowest Dependency:98.8
-
Efficiency (%):98.8
-
Modular UPS Module Tested Model Number:No
-
Energy Storage Mechanism:Battery
-
Energy Storage System Technology:Valve Regulated Lead-acid Battery
-
Energy Storage System Configuration:Integral
-
Energy Storage System Removable to Another Room:No
-
Energy Storage System Runtime at 100% Load (min.):5
-
Energy Storage System Runtime at 50% Load (min.):13
-
Energy Storage System Warranty (yrs):3
-
Energy Storage System Information URL:http://www.cyberpowersystems.com
-
Network Connections Available:Serial Port,USB Port,Ethernet
-
Communication Protocols:HTTPS,SNMP (v1, 2 or 3),HTTP
-
Data Provided via Network Communication:Output Active Power,Output Voltage
-
Data Visually Displayed:Output Active Power,Output Voltage
-
Output Energy Meter Integral or External to the UPS:No Energy Meter
-
Meets ENERGY STAR Optional Metering Requirements:N/A
-
Manufacturer Take Back Program:Yes
-
Model Web Page URL:http://www.cyberpowersystems.com
-
Meets Efficiency Requirements Without the Metering Incentive :N/A
-
Test Method Guidelines:http://www.cyberpowersystems.com
-
Date Available on Market:09/18/2013
-
Date Qualified:09/06/2013
-
Markets:United States
Additional Model Information
Follow us