« back Certified Uninterruptible Power Supplies

CyberPower - PR3000LCDRT2U

  • Power Conversion Mechanism:
    Static
  • Minimum Configuration Tested Model Number:
    PR3000LCDRT2U
  • Rated Output Power (W):
    2,250
  • Active Output Power Rating Minimum Configuration (W):
    2250
  • Apparent Output Power Rating Minimum Configuration (VA):
    3000
  • Topology (ac):
    Line Interactive
  • Topology and Product Type Combined:
    ac Line Interactive (VI)
  • Application:
    Data Center
  • Rated Input Voltage (V rms):
    80-150
  • Rated Input Frequency (Hz):
    47-63
  • Rated Output Voltage (V):
    125-125
  • Rated Output Frequency (Hz):
    47-63
  • Rack Mountable:
    Yes
  • Height (mm):
    88
  • Width (mm):
    495
  • Depth (mm):
    438
  • Total Number of Outlets:
    9
  • Number of Battery Backup and Surge Protected Outlets:
    9
  • Number of Surge Protected Only Outlets:
    0
  • Normal Mode(s) Input Dependency Characteristic (ac):
    Voltage Independent
  • Modular UPS:
    No
  • Number of Normal Modes:
    Single-normal-mode
  • Default Normal Mode (ac):
    Voltage Independent
  • Test Input Voltage (V rms):
    125
  • Test Input Frequency (Hz):
    60
  • Test Output Voltage (V):
    125
  • Test Output Frequency (Hz):
    60
  • Total Input Power in W at 0% Load Min Config Lowest Dependency (ac):
    10.0
  • Efficiency at 25% Load Min Config Lowest Dependency (ac):
    98.3
  • Efficiency at 50% Load Min Config Lowest Dependency (ac):
    98.8
  • Efficiency at 75% Load Min Config Lowest Dependency (ac):
    98.5
  • Efficiency at 100% Load Min Config Lowest Dependency (ac):
    98.3
  • Weighted Efficiency Calc Min Config Lowest Dependency:
    98.5
  • Efficiency (%):
    98.5
  • Modular UPS Module Tested Model Number:
    N/A
  • Energy Storage Mechanism:
    Battery
  • Energy Storage System Technology:
    Valve Regulated Lead-acid Battery
  • Energy Storage System Configuration:
    Integral
  • Energy Storage System Removable to Another Room:
    Yes
  • Energy Storage System Runtime at 100% Load (min.):
    3
  • Energy Storage System Runtime at 50% Load (min.):
    8
  • Energy Storage System Warranty (yrs):
    2
  • Energy Storage System Information URL:
    N/A
  • Network Connections Available:
    Serial Port,USB Port,Ethernet
  • Communication Protocols:
    Other,SNMP (v1, 2 or 3),HTTP
  • Communication Protocol Other:
    TCP/IP, UDP
  • Data Provided via Network Communication:
    Output Active Power,Output Voltage
  • Data Visually Displayed:
    Output Active Power,Output Voltage
  • Output Energy Meter Integral or External to the UPS:
    No Energy Meter
  • Meets ENERGY STAR Optional Metering Requirements:
    N/A
  • Manufacturer Take Back Program:
    Yes
  • Model Web Page URL:
    http://www.cpsww.com/
  • Meets Efficiency Requirements Without the Metering Incentive :
    N/A
  • Test Method Guidelines:
    N/A
  • Date Available on Market:
    04/11/2012
  • Date Qualified:
    11/01/2012
  • Markets:
    United States

Additional Model Information