Home > Partner Resources > Third-Party Certification > Certification Body Resources > XML Web Services Submission Process > ENERGY STAR Ac-output Uninterruptible Power Supplies (UPS) Template

ENERGY STAR Ac-output Uninterruptible Power Supplies (UPS) Template

Service Method: Submit_Ac_output_Uninterruptible_Power_Supplies_UPS_1_x
Version Number: V1 AC
Description: Information for certification bodies to provide to EPA on Ac-output Uninterruptible Power Supply (UPS) products certified as meeting the eligibility criteria for the ENERGY STAR® Program Requirements for Uninterruptible Power Supplies Version 1.0. Additional instructions for submitting this information to EPA are available at www.energystar.gov/cbresources.
History Subscribe to updates via RSS 2.0:
  • 07/26/12 - Submit_AC_Output_Uninterruptible_Power_Supplies_1_x Final
  • 06/15/12 - Submit_AC_Output_Uninterruptible_Power_Supplies_1_x Available for Testing
Name Description Required/ Optional Multiple Select Data Type Restrictions Enumerations
ENERGY STAR Manufacturing Partner The ENERGY STAR Manufacturing Partner is the organization that has signed an ENERGY STAR Partnership Agreement and labels the model. This organization is typically the brand owner. R N Text Min Length: 1
Max Length: 80
ENERGY STAR Manufacturing Partner's EPA-issued Organization ID This EPA-issued ID is the number assigned to the ENERGY STAR Manufacturing Partner. This ID can be located via the certification body's My ENERGY STAR Account (MESA) and searching for the organization's name. R N Integer
Partner Contact Name for This Model Provide the ENERGY STAR Manufacturing Partner contact responsible for this certified model. R N Text Min Length: 1
Max Length: 200
Type of Transaction Include the Type of Transaction associated with the certified model. Only the options included in the enumeration list may be provided. Initial certification must only be used if the model has never been submitted and does not have an ENERGY STAR Model Identifier. Registration must only be used for select types of models where EPA allows certification bodies to add previously qualified models to their programs for purposes of verification testing only. Modification must be used for administrative changes, including rerating the model(s). Certification withdrawn must be used when the model is no longer certified as ENERGY STAR. Recertification will rarely be used and must be approved by EPA prior to the transaction. R N Enumeration Data
  • Initial Certification
  • Modification
  • Certification Withdrawn
  • Recertification
  • Registration
Reason for Transaction Include the Reason for Transaction associated with the Type of Transaction. Only the reasons included in the enumeration list may be provided. If "other" is provided, list further details in the notes field. The certification body will determine when it is appropriate to use the reasons associated with "Initial Certification," "Registration" or "Modification." The reasons "Manufacturer Voluntary Withdrawal" and "No Longer Available" may be determined by the certification body and must only be associated with the transaction type "Certification Withdrawn." For all other cases of "Certification Withdrawn" or "Recertification," EPA must determine the appropriate reason and provide direction to the certification body. R N Enumeration Data
  • Initial Certification: Model Meets ENERGY STAR Requirements
  • Registration: Included in Verification Testing Pool
  • Modification: Added Model Name/Number
  • Modification: Removed Model Name/Number
  • Modification: Changed Model Name/Number
  • Modification: Changed Data
  • Modification: Rerated Models
  • Modification: Other (If Other, List in Notes Field)
  • Certification Withdrawn: No Longer Available
  • Certification Withdrawn: Manufacturer Voluntary Withdrawal
  • Certification Withdrawn: Delisted - Issue with Partnership
  • Certification Withdrawn: Disqualified Model - Failed Testing
  • Certification Withdrawn: Other (If Other, List in Notes Field)
  • Recertification: Model Meets ENERGY STAR Requirements
  • Recertification: Other (If Other, List in Notes Field)
Date of Transaction Type This date must be the same as the date when the Type of Transaction occurred. For example, the initial certification date must be the date the certification body notified the partner of model certification. R N Date
ENERGY STAR Model Identifier ENERGY_STAR_Model_Identifier is a unique string of characters generated by certification bodies in accordance with EPA's ENERGY_STAR_Model_Identifier standard. ENERGY_STAR_Model_Identifier serves to distinguish models with non-identical performance characteristics. A unique ENERGY_STAR_Model_Identifier must be assigned to each set of performance data that represents a model. Models in a family, series, or DOE basic model group that differ by one or more performance characteristics must be assigned different and unique ENERGY_STAR_Model_Identifiers. ENERGY_STAR_Model_Identifier is different from Certification_ID or Family_ID, which may apply to several models that differ in terms of reported attributes. Naming convention is as follows: ES_[[ManufacturerOID]]_[[MODELNUMBER]]_[[MMDDYYYYH24MISS]]_[[7 Digit-randomnumber]] Note : Total Max length of this must not exceed 400 characters. [[ManufacturerOID]] = Provide Manufacturer EPA issued O_ID [[MODELNUMBER]] = Provide Model Number of the model [[MMDDYYYYH24MISS]] = Create date time string in the format where MM= month number, DD - Day number, YYYY = Year number, H24 hours (0-23), MI minute number, SS seconds. This typically indicates the date of certification, but there are no validations performed on it. [[7 Digit-randomnumber]] = Provide a random number of seven digits. R N Text Min Length: 1
Max Length: 400
Certification ID Certification_ID is a unique string of characters generated by certification bodies in accordance with EPA's Certifcation_ID standard. Certification_ID serves to distinguish one or more models with differing performance characteristics under a single certification in order to track models associated with that certification. Naming convention for Certification_ID is as follows: CER_[[ManufacturerOID]]_[[MMDDYYYYH24MISS]]_[[7 Digit-randomnumber]] Note : Total Max length of this must not exceed 400 characters. [[ManufacturerOID]] = Provide Manufacturer EPA issues O_ID, [[MMDDYYYYH24MISS]] = Create date time string in the format where MM= month number, DD - Day number, YYYY = Year number, H24 hours (0-23), MI minute number, SS seconds. This typically indicates the date of certification, but there are no validations performed on it. [[7 Digit-randomnumber]] = Provide a random number of seven digits. R N Text Min Length: 1
Max Length: 400
Family ID Family_ID is a unique string of characters generated by certification bodies in accordance with EPA's Family_ID standard. Family_ID serves to identify models under the same certification that are part of the same model family, series, or DOE basic model group. Family_ID may only be included for models where the ENERGY STAR specification supports families. *NOTE* Under a single certification, certification bodies may or may not have a Family_ID listed. A Family_ID must not be listed if the certification is comprised of only a single model. If there is a Family_ID listed, all models within the certification listed must also have the same Family_ID. Naming conventions for Family_ID are as follows: FAM_[[ManufacturerOID]]_[[MMDDYYYYH24MISS]]_[[7 Digit-randomnumber]] Note : Total Max length of this must not exceed 400 characters. [[ManufacturerOID]] = Provide Manufacturer EPA issues O_ID, [[MMDDYYYYH24MISS]] = Create date time string in the format where MM= month number, DD - Day number, YYYY = Year number, H24 hours (0-23), MI minute number, SS seconds. This typically indicates the date of certification, but there are no validations performed on it. [[7 Digit-randomnumber]] = Provide a random number of seven digits. O N Text Max Length: 400
Model Name Provide the Model Name of the certified model. If the certified model is part of a model family, include the family model name. The use of wildcards is allowed, but may limit the ability to search for a specific model name. R N Text Min Length: 1
Max Length: 255
Model Number Provide the Model Number of the certified model. If the certified model is part of a model family, include the family model number. The use of wildcards is allowed, but may limit the ability to search for a specific model name. R N Text Min Length: 1
Max Length: 255
Brand Name Provide the model Brand Name in this field. To aid with consumer model searches, use consistent spelling, punctuation, and capitalization when providing brand names. R N Text Min Length: 1
Max Length: 200
Tested Model Name Provide the model name of the specific model that was tested. This will be the same as the Model Name unless this is a model family or private labeling submission. R N Text Min Length: 1
Max Length: 255
Tested Model Number Provide the model number of the specific model that was tested. This will be the same as the Model Number unless this is a model family or private labeling submission. R N Text Min Length: 1
Max Length: 255
Additional Models Represented by Family, Series, or DOE Basic Model
Additional Models Represented by Family, Series, or DOE Basic Model Additional Models Represented by Family, Series, or DOE Basic Model allows the listing of multiple additional models that are part of the same certification where performance characteristics are the same. The additional models may be identified by multiple sets of a model name and/or model number and/or additional identifying information. Each uniquely identified additional model name/number/identifier set must be listed as a separate entry within this field and must not be a comma-separated list. The use of wildcards is allowed, but may limit the ability to search for specific additional model names/numbers/identifiers. O Y
  • Additional Model Name
Provide each Additional Model Name as a separate data entry. O N Text Max Length: 255
  • Additional Model Number
Provide each Additional Model Number as a separate data entry. O N Text Max Length: 255
  • Additional Identifying Information
Provide any Additional Identifying Information associated with the Model Name and/or Model Number. The identifying information may be used by consumers, incentive programs, or retailers to identify this model or model family. This includes, but is not limited to, SKUs, UPC codes, retail numbers, and/or descriptions of models included/not included in the reported Model Family. Provide each Additional Identifying Information as a separate data entry. O N Text Max Length: 255
Is the Partner Listed the Original Equipment Manufacturer (OEM)? Indicate whether or not the ENERGY STAR Manufacturing Partner that labels this model also manufactures this model. R N Enumeration Data
  • Yes
  • No
If the Partner is not the Original Equipment Manufacturer, Who Is? In the case that the manufacturer partner listed is not the original equipment manufacturer (OEM), provide the name of the OEM. The OEM is the organization that has manufactured the model. O N Text Max Length: 80
Currently Available on Market? If model is currently available, indicate "Yes." Otherwise, indicate "No." Note that all available models are displayed on an ENERGY STAR qualified product list and are subject to verification testing. R N Enumeration Data
  • Yes
  • No
Date Available on Market Date model is first sold within one or more markets. R N Date
Date Tested Date of laboratory test. If multiple test reports, provide the most recent date. R N Date
Date Certification Body Notified Partner of Model Certification. The date the certification body notifies the manufacturer that the model is certified as ENERGY STAR. R N Date
Certification Body Contact Name for this Model The name of the primary certification body contact responsible for any questions concerning the certification of the model. R N Text Min Length: 1
Max Length: 200
Laboratory
Laboratory Include information about one or more laboratories in which the model was tested. O Y
  • Laboratory's EPA-issued Organization ID
This EPA-issued ID is the number assigned to the EPA-recognized laboratory that tested the model. This ID can be located via the certification body's My ENERGY STAR Account (MESA) and searching for the laboratory's name. This field is required for all certified models. O N Integer
  • Laboratory Contact for this Model
The name of the primary laboratory contact responsible for any questions concerning the testing of the model. This information is required for each laboratory indicated. O N Text Max Length: 200
In What Markets Is this Model Sold? Models must be sold in one or more of the ENERGY STAR partner markets provided in the enumeration list. R Y Enumeration Data
  • Australia
  • New Zealand
  • Canada
  • Europe
  • Japan
  • Switzerland
  • Taiwan
  • United States
Notes Provide any additional, relevant information related to the certification, including the reason for the transaction if "Other" is provided. O N Text Max Length: 2000
Ac_output_Uninterruptible_Power_Supplies_UPS info
ENERGY STAR Specification Version Provide the ENERGY STAR UPS specification version number. R N Enumeration Data
  • 1.0
Product Type Provide the UPS product type. R N Enumeration Data
  • Ac-output UPS
Model Meets Definition of Modular UPS Indicate whether the model meets the definition of Modular UPS. R N Enumeration Data
  • Yes
  • No
Minimum Configuration Tested Model Number For non-Modular UPS, provide the model number of the tested unit. For a Modular UPS Product Family, provide the model number of the tested minimum configuration unit. This model number will appear on the ENERGY STAR list of qualified products. R N Text Min Length: 1
Max Length: 255
Maximum Configuration Tested Model Number Required for a Modular UPS Product Family only. Provide the model number of the unit tested as the maximum configuration. This model number will appear on the ENERGY STAR list of qualified products. O N Text Max Length: 255
Modular UPS Module Tested Model Number Required for all models meeting the definition of Modular UPS. Provide the model or part number of the installed module(s) in the specific tested model’s chassis of the unit under test. Indicate N/A if the unit is not a Modular UPS or if there were no modules installed during testing. R N Text Min Length: 1
Max Length: 255
Power Conversion Mechanism Indicate the Power Conversion Mechanism of the model. R N Enumeration Data
  • Static
  • Rotary
Topology Indicate the Topology of the model. If the Topology is not listed, please indicate Other. R N Enumeration Data
  • Passive Standby
  • Line Interactive
  • Double Conversion
  • Multi-Mode Double Conversion
  • Multi-Mode Line Interactive
  • Other
Topology Other Required if the Topology is Other. Provide the Topology. O N Text Max Length: 100
Application Indicate the intended application(s) for the model. Consumer models are intended to protect desktop computers and related peripherals, and/or home entertainment devices such as TVs, set-top boxes, DVRs, Blu-ray and DVD players. Commercial models are intended to protect small business and branch office information and communication technology equipment such as servers, network switches and routers, and small storage arrays. Data Center models are intended to protect large installations of information and communication technology equipment such as enterprise servers, networking equipment, and large storage arrays. R Y Enumeration Data
  • Consumer
  • Commercial
  • Data Center
Rack Mountable Indicate whether the model is rack mountable. R N Enumeration Data
  • Yes
  • No
Rack Mount Height (U) Required for Rack Mountable models. Provide the rack mount height for the model in rack units or “U”, equal to 1.75 in (44.45 mm). O N Integer
Number of Normal Modes Indicate whether model is Single-normal-mode or Multiple-normal-mode. R N Enumeration Data
  • Single-normal-mode
  • Multiple-normal-mode
Normal Mode(s) Input Dependency Characteristic Indicate the input dependency characteristic(s) for each tested Normal Mode. R Y Enumeration Data
  • Voltage and Frequency Dependent
  • Voltage Independent
  • Voltage and Frequency Independent
Default Normal Mode Indicate the default Normal Mode of the model in its as-shipped configuration. R N Enumeration Data
  • Voltage and Frequency Dependent
  • Voltage Independent
  • Voltage and Frequency Independent
Height (mm) Provide the physical height of the model in millimeters, not including any external energy storage system with separate enclosures. R N Integer Min Value: 1
Max Value: 10000
Width (mm) Provide the physical width of the model in millimeters, not including any external energy storage system with separate enclosures. R N Integer Min Value: 1
Max Value: 10000
Depth (mm) Provide the physical depth of the model in millimeters, not including any external energy storage system with separate enclosures. R N Integer Min Value: 1
Max Value: 10000
Minimum Input Voltage (V rms) Provide the minimum rated input voltage of the model. R N Integer Min Value: 1
Maximum Input Voltage (V rms) Provide the maximum rated input voltage of the model. R N Integer Min Value: 1
Minimum Input Frequency (Hz) Provide the minimum rated input frequency of the model. R N Integer Min Value: 1
Maximum Input Frequency (Hz) Provide the maximum rated input frequency of the model. R N Integer Min Value: 1
Minimum Output Voltage (V rms) Provide the minimum rated output voltage of the model. R N Integer Min Value: 1
Maximum Output Voltage (V rms) Provide the maximum rated output voltage of the model. R N Integer Min Value: 1
Minimum Output Frequency (Hz) Provide the minimum rated output frequency of the model. R N Integer Min Value: 1
Maximum Output Frequency (Hz) Provide the maximum rated output frequency of the model. R N Integer Min Value: 1
Total Number of Outlets Required for models with output power less than or equal to 1500 W. Indicate the total number of outlets/output connections provided by the model. O N Integer
Number of Battery Backup and Surge Protected Outlets Required for models with output power less than or equal to 1500 W. Indicate the total number of battery backup and surge protected outlets provided by the model. O N Integer
Number of Surge Protected Only Outlets Required for models with output power less than or equal to 1500 W. Indicate the total number of surge protected only outlets provided by the model. O N Integer
Energy Storage Mechanism Indicate the type of energy storage mechanism. R N Enumeration Data
  • Battery
  • Flywheel
  • Other
  • N/A
Energy Storage Mechanism Other Required if Energy Storage Mechanism is Other. Specify the type of energy storage mechanism. O N Text Max Length: 50
Energy Storage System Configuration Indicate whether the energy storage system is integral to the model (i.e. installed in the chassis) or contained in a separate enclosure. R N Enumeration Data
  • Integral
  • Separate Enclosure
  • N/A
Energy Storage System Removable to Another Room Indicate whether the energy storage system can be removed from the UPS for placement in another room, to allow the placement of the UPS in an unconditioned space, saving energy. Indicate N/A if the energy storage system is integral to the model. R N Enumeration Data
  • Yes
  • No
  • N/A
Energy Storage System Connected During Test Indicate whether the energy storage system was connected during the test. R N Enumeration Data
  • Yes
  • No
  • N/A
Energy Storage System Part Number Provide the model or part number for the energy storage system used during the test. Indicate N/A if there is no energy storage system. R N Text Min Length: 1
Max Length: 255
Energy Storage System Technology Indicate the technology/chemistry of the energy storage system. R N Enumeration Data
  • Flywheel
  • Valve Regulated Lead-acid Battery
  • Vented Lead-acid Battery
  • Nickel-cadmium Battery
  • Lithium-ion Battery
  • Other
  • N/A
Energy Storage System Technology Other Required if Energy Storage System Technology is Other. Specify the energy storage system technology. O N Text Max Length: 50
Energy Storage System Runtime at 100% Load (min) Indicate the runtime at 100% resistive load of the energy storage system tested with the model in minutes. Indicate N/A if there is no energy storage system. R N Text Min Length: 1
Max Length: 1000
Energy Storage System Runtime at 50% Load (min) Indicate the runtime at 50% resistive load of the energy storage system tested with the model in minutes. Indicate N/A if there is no energy storage system. R N Text Min Length: 1
Max Length: 1000
Energy Storage System Warranty (yr) Provide the manufacturer warranty of the energy storage system tested with the model. Express warranty in number of years for finite values or as "lifetime warranty." Indicate N/A if there is no energy storage system. R N Text Min Length: 1
Max Length: 25
Test Method Guidelines Provide a web URL to the publicly available document that provides guidelines for implementing the ENERGY STAR Test Method. Indicate N/A if there are no additional guidelines. R N Text Min Length: 1
Max Length: 1000
Energy Storage System Information URL Provide a web URL to additional information about the energy storage system, such as configuration options; capacities; runtimes, etc. Information can be provided by the UPS Partner or an energy storage system vendor. Indicate N/A if there is no URL for the energy storage system. R N Text Min Length: 1
Max Length: 250
Meets ENERGY STAR Optional Metering Requirements Required if the rated output power is greater than 10,000 W. Indicate whether the model(s) meet(s) metering requirements. For models with output power less than or equal to 10,000 W, indicate N/A. R N Enumeration Data
  • Yes
  • No
  • N/A
Meets Efficiency Requirements without the Metering Incentive Indicate whether all models meet the average efficiency requirements without the metering incentive. For models with output power less than or equal to 10,000 W, indicate N/A. R N Enumeration Data
  • Yes
  • No
  • N/A
Output Energy Meter Integral or External to the UPS If the model is sold with an output energy meter, indicate whether the meter is integral (installed within the chassis) or external (bundled with the UPS system at point of sale) to the UPS model. Otherwise, indicate No Energy Meter. R N Enumeration Data
  • Integral Meter Installed
  • External Bundled Meter
  • No Energy Meter
External Meter Manufacturer and Model Name Required for models with a bundled external energy meter. Provide the manufacturer name and model name of the meter. O N Text Max Length: 255
External Meter URL Required for models with an external bundled meter. Provide a web URL for the external bundled meter if available. Otherwise, indicate N/A. O N Text Max Length: 250
Energy Measurement Accuracy Class Required if the model is sold with an external energy meter. Indicate the meter’s highest accuracy class as specified in IEC 62053-21, IEC 62053-22, or ANSI C12.1. If the meter does not meet an accuracy class as defined by an external standard, indicate N/A. O N Enumeration Data
  • IEC Class 1
  • IEC Class 2
  • IEC Class 0.5 S
  • IEC Class 0.2 S
  • ANSI Class 1
  • ANSI Class 2
  • ANSI Class 0.5 S
  • ANSI Class 0.2 S
  • N/A
Energy Measurement Meter-only Accuracy (%) Required if the external meter does not meet one of IEC or ANSI-defined accuracy classes. Indicate the meter's energy measurement accuracy expressed as a percentage at 25 and 100 percent of the meter’s maximum current. O N Decimal No. of Decimal: 2
Min Value: 0
Max Value: 5.00
Energy Measurement Metering System Accuracy (%) Required if the external meter is part of a complete measurement system or if the meter is integral. Indicate the metering system’s energy measurement accuracy expressed as a percentage under the conditions specified in the ENERGY STAR Test Method. O N Decimal No. of Decimal: 2
Min Value: 0
Max Value: 5.00
Data Visually Displayed Indicate which data are visually displayed on the model and/or meter. R Y Enumeration Data
  • Output Active Power
  • Output Accumulated Energy
  • Output Voltage
  • Output Current
  • Output Power Factor
  • No Display
Data Provided via Network Communication Indicate which data are provided via network communication capability on the model and/or meter. R Y Enumeration Data
  • Output Active Power
  • Output Accumulated Energy
  • Output Voltage
  • Output Current
  • Output Power Factor
  • No Network Communication
Network Connections Available Indicate the available connections for management of the model. R Y Enumeration Data
  • Serial Port
  • USB Port
  • Ethernet
  • Other
  • None
Communication Protocols Indicate the communication protocols available on the model and/or the meter. R Y Enumeration Data
  • Modbus RTU
  • Modbus TCP
  • SNMP (v1, 2 or 3)
  • HTTP
  • HTTPS
  • Other
  • None
Communication Protocol Other Required if Communication Protocols is Other. Specify the type. O N Text Max Length: 25
User Meter-interface Software Included Indicate whether the model ships with end-user software capable of interfacing with the meter to permit remote monitoring of the efficiency of the UPS. R N Enumeration Data
  • Yes
  • No
Manufacturer Take Back Program Indicate whether the manufacturer offers a UPS take-back program in the U.S. R N Enumeration Data
  • Yes
  • No
Manufacturer Take Back Program URL Required if a web URL to the manufacturer take-back or recycling program for UPSs is available. O N Text Max Length: 250
Life Cycle Assessment URL Required if a web URL to the life-cycle assessment of the model is available. O N Text Max Length: 250
Battery Recycling URL Required if a web URL to battery recycling information is available. O N Text Max Length: 250
Model Web Page URL Provide a URL for the model’s consumer-facing web page located on the Partner's website. R N Text Min Length: 1
Max Length: 250
Test Input Voltage (V rms) Provide the input voltage used during test. R N Integer Min Value: 1
Test Input Frequency (Hz) Provide the input frequency used during test. R N Integer Min Value: 1
Test Output Voltage (V rms) Provide the output voltage used during test. R N Integer Min Value: 1
Test Output Frequency (Hz) Provide the output frequency used during test. R N Integer Min Value: 1
Apparent Output Power Rating Min Config (VA) Provide the apparent output power rating in VA of the minimum configuration tested model. The minimum configuration tested model applies to the single unit tested for non-Modular UPS and the minimum configuration unit tested for Modular UPS. R N Integer Min Value: 1
Active Output Power Rating Min Config (W) Provide the active output power rating in W of the minimum configuration tested model. R N Integer Min Value: 1
Input Power Factor Min Config Lowest Dependency Provide the measured input power factor at 100% load of the minimum configuration model in the lowest input dependency mode. R N Decimal No. of Decimal: 2
Min Value: 0.00
Max Value: 1.00
Calculated Efficiency at 100% Load Min Config Lowest Dependency Provide Calculated Efficiency at 100% Load expressed as a decimal for minimum configuration model based on measured test data in the lowest input dependency mode. R N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 100% Load Min Config Lowest Dependency Provide the Reported Efficiency at 100% Load expressed as a decimal for the minimum configuration model in the lowest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. R N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Calculated Efficiency at 75% Load Min Config Lowest Dependency Provide the Calculated Efficiency at 75% Load expressed as a decimal for the minimum configuration model based on measured test data in the lowest input dependency mode. R N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 75% Load Min Config Lowest Dependency Provide the Reported Efficiency at 75% Load expressed as a decimal for the minimum configuration model in the lowest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. R N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Calculated Efficiency at 50% Load Min Config Lowest Dependency Provide the Calculated Efficiency at 50% Load expressed as a decimal for the minimum configuration model based on measured test data in the lowest input dependency mode. R N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 50% Load Min Config Lowest Dependency Provide the Reported Efficiency at 50% Load expressed as a decimal for the minimum configuration model in the lowest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. R N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Calculated Efficiency at 25% Load Min Config Lowest Dependency Provide the Calculated Efficiency at 25% Load expressed as a decimal for the minimum configuration model based on measured test data in the lowest input dependency mode. R N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 25% Load Min Config Lowest Dependency Provide the Reported Efficiency at 25% Load expressed as a decimal for the minimum configuration model in the lowest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. R N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Total Input Power at 0% Load Min Config Lowest Dependency (W) Provide the Total Real Input Power at 0% Load in W for the minimum configuration model in the lowest input dependency mode. R N Decimal
Reported Weighted Efficiency Calc Min Config Lowest Dependency Provide the Reported Calculation of Average Efficiency expressed as a decimal for the minimum configuration tested model in the lowest input dependency per Equation 1 in the specification. This value will appear on the ENERGY STAR list of qualified products and UPS Power and Performance Data Sheet. R N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Input Power Factor Min Config Highest Dependency Required for Multiple-normal-mode UPS. Provide the measured input power factor at 100% load of the minimum configuration model tested in the highest input dependency mode. O N Decimal No. of Decimal: 2
Min Value: 0.00
Max Value: 1.00
Calculated Efficiency at 100% Load Min Config Highest Dependency Required for Multiple-normal-mode UPS. Provide the Calculated Efficiency at 100% Load expressed as a decimal for the minimum configuration model based on measured data in the highest input dependency mode. O N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 100% Load Min Config Highest Dependency Required for Multiple-normal-mode UPS. Provide the Reported Efficiency at 100% Load expressed as a decimal for the minimum configuration model tested in the highest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Calculated Efficiency at 75% Load Min Config Highest Dependency Required for Multiple-normal-mode UPS. Provide the Calculated Efficiency at 75% Load expressed as a decimal for the minimum configuration model based on measured test data in the highest input dependency mode. O N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 75% Load Min Config Highest Dependency Required for Multiple-normal-mode UPS. Provide the Reported Efficiency at 75% Load expressed as a decimal for the minimum configuration model in the highest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Calculated Efficiency at 50% Load Min Config Highest Dependency Required for Multiple-normal-mode UPS. Provide the Calculated Efficiency at 50% Load expressed as a decimal for the minimum configuration model based on measured test data in the highest input dependency mode. O N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 50% Load Min Config Highest Dependency Required for Multiple-normal-mode UPS. Provide the Reported Efficiency at 50% Load expressed as a decimal for the minimum configuration model in the highest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Calculated Efficiency at 25% Load Min Config Highest Dependency Required for Multiple-normal-mode UPS. Provide the Calculated Efficiency at 25% Load expressed as a decimal for the minimum configuration model based on measured test data in the highest input dependency mode. O N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 25% Load Min Config Highest Dependency Required for Multiple-normal-mode UPS. Provide the Reported Efficiency at 25% Load expressed as a decimal for the minimum configuration model in highest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Total Input Power at 0% Load Min Config Highest Dependency (W) Required for Multiple-normal-mode UPS. Provide the Total Real Input Power at 0% Load in W for the minimum configuration model in the highest input dependency mode. O N Decimal
Reported Weighted Efficiency Calc Min Config Highest Dependency Required for Multiple-normal-mode UPS. Provide the Reported Calculation of Average Efficiency expressed as a decimal for the minimum configuration model in the highest input dependency per Equation 1 in the specification. This value will appear on the ENERGY STAR list of qualified products and the UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Reported Avg Efficiency for Multiple-normal-mode UPS Min Config Required for Multiple-normal-mode UPS. Provide the Reported Multiple-normal-mode UPS Calculation of Average Efficiency expressed as a decimal for the minimum configuration tested model per Equation 2 in the specification. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
ENERGY STAR Min Avg Efficiency Requirement Min Config Include the Average Efficiency Requirement for the tested active output power and lowest available input dependency of minimum configuration model per the specification. Value must be expressed as a decimal. R N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Apparent Output Power Rating Max Config (VA) Required for a Modular UPS Product Family. Provide the apparent output power rating in VA of the maximum configuration tested model. O N Integer
Active Output Power Rating Max Config (W) Required for a Modular UPS Product Family. Provide the active output rating power in W of the maximum configuration tested model. O N Integer
Input Power Factor Max Config Lowest Dependency Required for a Modular UPS Product Family. Provide the measured input power factor at 100% load of the maximum configuration model in the lowest input dependency mode. O N Decimal No. of Decimal: 2
Min Value: 0.00
Max Value: 1.00
Calculated Efficiency at 100% Load Max Config Lowest Dependency Required for a Modular UPS Product Family. Provide the Calculated Efficiency at 100% Load expressed as a decimal for the maximum configuration model based on measured test data in the lowest input dependency mode. O N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 100% Load Max Config Lowest Dependency Required for a Modular UPS Product Family. Provide the Reported Efficiency at 100% Load expressed as a decimal for the maximum configuration model tested in the lowest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Calculated Efficiency at 75% Load Max Config Lowest Dependency Required for a Modular UPS Product Family. Provide the Calculated Efficiency at 75% Load expressed as a decimal for the maximum configuration model based on measured test data in the lowest input dependency mode. O N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 75% Load Max Config Lowest Dependency Required for a Modular UPS Product Family. Provide the Reported Efficiency at 75% Load expressed as a decimal for the maximum configuration model tested in the lowest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Calculated Efficiency at 50% Load Max Config Lowest Dependency Required for a Modular UPS Product Family. Provide the Calculated Efficiency at 50% Load expressed as a decimal for the maximum configuration model based on measured test data in the lowest input dependency mode. O N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 50% Load Max Config Lowest Dependency Required for a Modular UPS Product Family. Provide the Reported Efficiency at 50% Load expressed as a decimal for the maximum configuration model tested in the lowest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Calculated Efficiency at 25% Load Max Config Lowest Dependency Required for a Modular UPS Product Family. Provide the Calculated Efficiency at 25% Load expressed as a decimal for the maximum configuration model based on measured test data in the lowest input dependency mode. O N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 25% Load Max Config Lowest Dependency Required for a Modular UPS Product Family. Provide the Reported Efficiency at 25% Load expressed as a decimal for the maximum configuration model in the lowest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Total Input Power at 0% Load Max Config Lowest Dependency (W) Required for a Modular UPS Product Family. Provide the Total Real Input Power at 0% Load in W for the maximum configuration model tested in the lowest input dependency mode. O N Decimal
Reported Weighted Efficiency Calc Max Config Lowest Dependency Required for a Modular UPS Product Family. Provide the Calculation of Average Efficiency expressed as a decimal for the maximum configuration model tested in the lowest input dependency per Equation 1 in the specification. This value will appear on the ENERGY STAR list of qualified products and UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Input Power Factor Max Config Highest Dependency Required for a Modular Multiple-normal-mode UPS Product Family. Provide the measured input power factor at 100% load of the maximum configuration model tested in the highest input dependency mode. O N Decimal No. of Decimal: 2
Min Value: 0.00
Max Value: 1.00
Calculated Efficiency at 100% Load Max Config Highest Dependency Required for a Modular Multiple-normal-mode UPS Product Family. Provide the Calculated Efficiency at 100% Load expressed as a decimal for the maximum configuration model based on measured test data in the highest input dependency mode. O N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 100% Load Max Config Highest Dependency Required for a Modular Multiple-normal-mode UPS Product Family. Provide the Reported Efficiency at 100% Load expressed as a decimal for the maximum configuration model in the highest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Calculated Efficiency at 75% Load Max Config Highest Dependency Required for a Modular Multiple-normal-mode UPS Product Family. Provide the Calculated Efficiency at 75% Load expressed as a decimal for the maximum configuration model based on measured test data in the highest input dependency mode. O N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 75% Load Max Config Highest Dependency Required for a Modular Multiple-normal-mode UPS Product Family. Provide the Reported Efficiency at 75% Load expressed as a decimal for the maximum configuration model in the highest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Calculated Efficiency at 50% Load Max Config Highest Dependency Required for a Modular Multiple-normal-mode UPS Product Family. Provide the Calculated Efficiency at 50% Load expressed as a decimal for the maximum configuration model based on measured test data in the highest input dependency mode. O N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 50% Load Max Config Highest Dependency Required for a Modular Multiple-normal-mode UPS Product Family. Provide the Reported Efficiency at 50% Load expressed as a decimal for the maximum configuration model in the highest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Calculated Efficiency at 25% Load Max Config Highest Dependency Required for a Modular Multiple-normal-mode UPS Product Family. Provide the Calculated Efficiency at 25% Load expressed as a decimal for the maximum configuration model based on measured test data in the highest input dependency mode. O N Decimal Min Value: 0.000
Max Value: 1.000
Reported Efficiency at 25% Load Max Config Highest Dependency Required for a Modular Multiple-normal-mode UPS Product Family. Provide the Reported Efficiency at 25% Load expressed as a decimal for the maximum configuration model in the highest input dependency mode. This value will appear on the ENERGY STAR UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Total Input Power at 0% Load Max Config Highest Dependency (W) Required for a Modular Multiple-normal-mode UPS Product Family. Provide the Total Real Input Power at 0% Load in W for the maximum configuration model in the highest input dependency mode. O N Decimal
Reported Weighted Efficiency Calc Max Config Highest Dependency Required for a Modular Multiple-normal-mode UPS Product Family. Provide the Reported Calculation of Average Efficiency expressed as a decimal for the maximum configuration model in the highest input dependency per Equation 1 in the specification. This value will appear on the ENERGY STAR list of qualified products list and the UPS Power and Performance Data Sheet. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
Reported Avg Efficiency for Multiple-normal-mode UPS Max Config Required for a Modular Multiple-normal-mode UPS Product Family. Provide the Reported Multiple-normal-mode UPS Calculation of Average Efficiency expressed as a decimal for the maximum configuration tested model per Equation 2 in the specification. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000
ENERGY STAR Min Avg Efficiency Requirement Max Config Required for a Modular UPS Product Family. Include the Average Efficiency Requirement for the tested active output power and lowest available input dependency of the maximum configuration tested model per the specification. Value must be expressed as a decimal. O N Decimal No. of Decimal: 3
Min Value: 0.000
Max Value: 1.000

Information for certification bodies to provide to EPA on Ac-output Uninterruptible Power Supply (UPS) products certified as meeting the eligibility criteria for the ENERGY STAR® Program Requirements for Uninterruptible Power Supplies Version 1.0. Additional instructions for submitting this information to EPA are available at www.energystar.gov/cbresources.